Description
It is designed to detect gas leaks in enclosed areas such as houses, garages, and similar indoor environments, and to provide audible and visual alarms. The detectors must not be used in open or semi-open areas such as terraces and balconies. Classification: Type 1 (devices designed for use in residential or light industrial environments) The ML-221X / ML-222X series is compatible with all conventional fire alarm panels. It operates with a 24V DC supply voltage via an external power source.
◗ Compliant with EN 50194-1, EN 50270, and EN 61000-6-3 standards
◗ Capable of detecting LPG/Methane gases within a 50 m² area using a single detector
◗ Provides alarm when the gas concentration reaches (15±5)% LEL alarm threshold
◗ Model options available for detecting LPG (Butane + Propane) and Natural Gas (Methane)
◗ For relay models with 10A relay: relay output capacity of 10A-250V AC / 5A-30V DC; for relay models with 0.5A relay: relay output capacity of 100mA 50V DC
◗ High sensitivity detection with semiconductor sensor technology
◗ Available in relay and non-relay versions
◗ Model option with built-in short circuit isolator
◗ IP42D protection rating
◗ Status indicators: Green – Power, Red – Alarm, Yellow – Fault LEDs
◗ Test Button for checking LED, Buzzer, and Relay functions
◗ Compatible with Maxlogic series conventional fire alarm panels
◗ Navy blue frame color for models detecting LPG
◗ Orange frame color for models detecting Natural Gas
MODELS |
|
| Product Code | Description |
| ML-292L | Maxlogic Gaz Dedektörü, LPG, 24V DC |
| ML-292L-R | Maxlogic Gas Detector, LPG, 24V DC, 10A Alarm Relay |
| ML-292L-RS | Maxlogic Gas Detector, LPG, 24V DC, 10A and 0.5A Alarm Relays |
| ML-292M | Maxlogic Gas Detector, Methane (Natural Gas), 24V DC |
| ML-292M-R | Maxlogic Gas Detector, Methane (Natural Gas), 24V DC, 10A Alarm Relay |
| ML-292M-RS | Maxlogic Gas Detector, Methane (Natural Gas), 24V DC, 10A and 0.5A Alarm Relays |
MODELS |
|
| Product Code | Description |
| ML-293L | Maxlogic Gas Detector, LPG, 230V AC |
| ML-293L-R | Maxlogic Gas Detector, LPG, 230V AC, 10A Alarm Relay |
| ML-293L-RS | Maxlogic Gas Detector, LPG, 230V AC, 10A and 0.5A Alarm Relays |
| ML-293M | Maxlogic Gas Detector, Methane (Natural Gas), 230V AC |
| ML-293M-R | Maxlogic Gas Detector, Methane (Natural Gas), 230V AC, 10A Alarm Relay |
| ML-293M-RS | Maxlogic Gas Detector, Methane (Natural Gas), 230V AC, 10A and 0.5A Alarm Relays |